CFKFD - SULFURIC ACID, BATTERY ELCTROLYTE-STANDBY(FLOODED)

  • MSDS: CFKFD
  • Manufacturer: C AND D CHARTER POWER SYSTEMS INC
  • Product Name: SULFURIC ACID, BATTERY ELCTROLYTE-STANDBY(FLOODED)
  • National Stock Number: 6140-00-610-1410
Product Identification

Product ID:SULFURIC ACID, BATTERY ELCTROLYTE-STANDBY(FLOODED)
MSDS Date:01/23/1996
FSC:6140
NIIN:00-610-1410
MSDS Number: CFKFD

Responsible Party
C & D CHARTER POWER SYSTEMS INC
1400 UNION MEETING ROAD
BLUE BELL, PA 19422-0858
US

Emergency Phone: 215-619-2700

Info Phone: 610-828-9309

Preparer: S. J. KELLY

Cage: 80531

Contractor
NO VENDOR HAS BEEN NAMED FOR THIS LINE.
UNKNOW PLYMOUTH MEETING, PA 19462 US

Telephone: 800-255-3924

Cage: NO672

Ingredients

SULFURIC ACID (SARA 302/313) (CERCLA)

CAS: 7664-93-9

RTECS: WS5600000

Fraction By Weight: 29-35%

OSHA PEL 1 MG/M3

ACGIH TLV: 1 MG/M3/3 STEL; 9495

EPA Report Quantity: 1000 LBS

DOT Report Quantity: 1000 LBS


WATER

CAS: 7732-18-5

RTECS: ZC0110000

Fraction By Weight: 65-71%

Hazards

LD50 LC50 Mixture:ORAL LD50 (RAT) IS 2140 MG/KG
Routes of Entry: Inhalation:YES Skin:YES Ingestion:YES
Reports of Carcinogenicity:NTP:NO IARC:YES OSHA:NO
Health Hazards Acute and Chronic:ACUTE-TISSUE DESTRUCTION ON CONTACT.
MAY CAUSE 2ND & 3RD DEGREE BURNS OR BLINDESS. INGESTION WILL CAUSE
CORROSIVE BURNS ON CONTACT. MAY BE FATAL IF SWALLOWED.
CHRONIC-INHALATION OF MIST MAY CAUSE UPPE R RESPIRATORY IRRITATION
& PULMONARY EDEMA.
Explanation of Carcinogenicity:CONTAINS SULFURIC. SEE THE INDIVIDUAL
IARC REPORT FOR DETAILS OF CARCINOGENICITY UNDER "STRONG INORGANIC
ACID MIST".
Effects of Overexposure:IRRITATION OR BURNING OF EXPOSED TISSUES.
Medical Cond Aggravated by Exposure:RESPIRATORY DISORDERS MAY BE
AGGRAVATED BY PROLONGED IN HALATION OF MISTS.

First Aid

First Aid:SKIN/EYES: FLUSH W/WATER FOR 15 MINUTES. REMOVE CONTAMINATED
CLOTHING. IF IRRITATION CONTINUES, SEEK MEDICAL ATTENTION.
INGESTION:DO NOT INDUCE VOMITING. DRINK LARGE QUANTITIES OF MILK OR
WATER. GIVE CPR IF BREATHING HAS STOPPED. SEEK MEDICAL ATTENTION
IMMEDIATELY.

Fire Fighting

Extinguishing Media:DRY CHEMICAL, HALON, CARBON DIOXIDE.
Fire Fighting Procedures:SELF-CONTAINED BREATHING APPARATUS (SCBA) &
FULL PROTECTIVE CLOTHES.
Unusual Fire/Explosion Hazard:HYDROGEN GAS AND ACID MIST ARE GENERATED
UPON OVERCHARGE OR IN FIRES. VENTILATE AREA.

Accidental Release

Spill Release Procedures:NEUTRALIZE SPILL W/SODA ASH OR SODIUM
BICARBONATE UNTIL FIZZING STOPS. KEEP UNTRAINED INDIVIDUALS AWAY.
USE ADEQUATE VENTILATION, HYDROGEN GAS MAY BE GIVEN OFF DURING
NEUTRALIZATION. CONTAIN LARGE SPI LLS W/EARTH OR CLAY DIKES.
Neutralizing Agent:SODA ASH OR SODIUM BICARBONATE.

Handling

Handling and Storage Precautions:ADD WATER TO ACID AFTER NEUTRALIZATION
TO AVOID EXCESSIVE HEAT GENERATION. STORE IN COOL, DRY AREA AWAY
FROM RECTIVES & COMBUSTIBLES.
Other Precautions:DO NOT STORE IN SEALED, UNVENTED AREAS. PROVIDE
SECONDARY CONTAINMENT IF LARGE VOLUMES ARE STORED.

Exposure Controls

Respiratory Protection:NIOSH APPROVED ACID MIST RESPIRATOR, IF OSHA PEL
IS EXCEEDED.
Ventilation:USE MECHANICAL (GENERAL) VENTILATION IS SUFFICIENT DURING
NORMAL USE & HANDLING. 2-3 ROOM CHANGES/HOUR ARE RECOMMENDED.
Protective Gloves:RUBBER OR NEOPRENE GLOVES.
Eye Protection:GOGGLES OR SAFETY GLASSES + FACE SHIELD
Other Protective Equipment:ACID RESISTANT APRON OR CLOTHING.
Work Hygienic Practices:MAINTAIN EYEWASH & DRENCH SHOWER IN AREA.
Supplemental Safety and Health
CONTACT C & D SALES REPRESENTATIVE FOR INFORMATION ON BATTERY (LEAD &
ACID) RECYCLING.

Chemical Properties

HCC:C1
NRC/State Lic Num:NONE
Boiling Pt:B.P. Text:235F,113C
Melt/Freeze Pt:M.P/F.P Text:N/A.
Vapor Pres:145.8 MM
Vapor Density:<1
Spec Gravity:1.215-1.290
Evaporation Rate & Reference:<1 , WATER=1
Solubility in Water:100%
Appearance and Odor:CLEAR COLORLESS LIQUID, ACRID SMELL.
Corrosion Rate:UNKNOWNN

Stability

Stability Indicator/Materials to Avoid:YES
METALS, COMBUSTIBLES.
Stability Condition to Avoid:THIS IS A STABLE MATERIAL.
Hazardous Decomposition Products:HYDROGEN GAS, SULFUR TRIOXIDE MAY BE
GENERATED DURING BATTERY OVERCHARGE & AT HIGH TEMPERATURES.
Conditions to Avoid Polymerization:WILL NOT OCCUR.

Disposal

Waste Disposal Methods:BATTERY ACID IS A CORROSIVE HAZARDOUS WASTE.
WHEN NEURTALIZED TO PH 6-8 IT IS NO LONGER HAZARDOUS. FOLLOW PROPER
DISPOSAL METHODS AS ALLOWED BY LOCAL ORDINANCES & SITE PERMITS.
ACID IN SCRAP BATTERIES WILL BE RECYCLED BY THE LEAD
RECYCLINGPROCESS.

Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.