CFKFD - SULFURIC ACID, BATTERY ELCTROLYTE-STANDBY(FLOODED)
- MSDS: CFKFD
- Manufacturer: C AND D CHARTER POWER SYSTEMS INC
- Product Name: SULFURIC ACID, BATTERY ELCTROLYTE-STANDBY(FLOODED)
- National Stock Number: 6140-00-610-1410
Product Identification
Product ID:SULFURIC ACID, BATTERY ELCTROLYTE-STANDBY(FLOODED)
MSDS Date:01/23/1996
FSC:6140
NIIN:00-610-1410
MSDS Number: CFKFD
Responsible Party
BLUE BELL, PA 19422-0858
US
Emergency Phone: 215-619-2700
Info Phone: 610-828-9309
Preparer: S. J. KELLY
Cage: 80531
Contractor
Telephone: 800-255-3924
Cage: NO672
Ingredients
SULFURIC ACID (SARA 302/313) (CERCLA)
CAS: 7664-93-9
RTECS: WS5600000
Fraction By Weight: 29-35%
OSHA PEL 1 MG/M3
ACGIH TLV: 1 MG/M3/3 STEL; 9495
EPA Report Quantity: 1000 LBS
DOT Report Quantity: 1000 LBS
WATER
CAS: 7732-18-5
RTECS: ZC0110000
Fraction By Weight: 65-71%
Hazards
LD50 LC50 Mixture:ORAL LD50 (RAT) IS 2140 MG/KG
Routes of Entry: Inhalation:YES Skin:YES Ingestion:YES
Reports of Carcinogenicity:NTP:NO IARC:YES OSHA:NO
Health Hazards Acute and Chronic:ACUTE-TISSUE DESTRUCTION ON CONTACT.
MAY CAUSE 2ND & 3RD DEGREE BURNS OR BLINDESS. INGESTION WILL CAUSE
CORROSIVE BURNS ON CONTACT. MAY BE FATAL IF SWALLOWED.
CHRONIC-INHALATION OF MIST MAY CAUSE UPPE R RESPIRATORY IRRITATION
& PULMONARY EDEMA.
Explanation of Carcinogenicity:CONTAINS SULFURIC. SEE THE INDIVIDUAL
IARC REPORT FOR DETAILS OF CARCINOGENICITY UNDER "STRONG INORGANIC
ACID MIST".
Effects of Overexposure:IRRITATION OR BURNING OF EXPOSED TISSUES.
Medical Cond Aggravated by Exposure:RESPIRATORY DISORDERS MAY BE
AGGRAVATED BY PROLONGED IN HALATION OF MISTS.
First Aid
First Aid:SKIN/EYES: FLUSH W/WATER FOR 15 MINUTES. REMOVE CONTAMINATED
CLOTHING. IF IRRITATION CONTINUES, SEEK MEDICAL ATTENTION.
INGESTION:DO NOT INDUCE VOMITING. DRINK LARGE QUANTITIES OF MILK OR
WATER. GIVE CPR IF BREATHING HAS STOPPED. SEEK MEDICAL ATTENTION
IMMEDIATELY.
Fire Fighting
Extinguishing Media:DRY CHEMICAL, HALON, CARBON DIOXIDE.
Fire Fighting Procedures:SELF-CONTAINED BREATHING APPARATUS (SCBA) &
FULL PROTECTIVE CLOTHES.
Unusual Fire/Explosion Hazard:HYDROGEN GAS AND ACID MIST ARE GENERATED
UPON OVERCHARGE OR IN FIRES. VENTILATE AREA.
Accidental Release
Spill Release Procedures:NEUTRALIZE SPILL W/SODA ASH OR SODIUM
BICARBONATE UNTIL FIZZING STOPS. KEEP UNTRAINED INDIVIDUALS AWAY.
USE ADEQUATE VENTILATION, HYDROGEN GAS MAY BE GIVEN OFF DURING
NEUTRALIZATION. CONTAIN LARGE SPI LLS W/EARTH OR CLAY DIKES.
Neutralizing Agent:SODA ASH OR SODIUM BICARBONATE.
Handling
Handling and Storage Precautions:ADD WATER TO ACID AFTER NEUTRALIZATION
TO AVOID EXCESSIVE HEAT GENERATION. STORE IN COOL, DRY AREA AWAY
FROM RECTIVES & COMBUSTIBLES.
Other Precautions:DO NOT STORE IN SEALED, UNVENTED AREAS. PROVIDE
SECONDARY CONTAINMENT IF LARGE VOLUMES ARE STORED.
Exposure Controls
Respiratory Protection:NIOSH APPROVED ACID MIST RESPIRATOR, IF OSHA PEL
IS EXCEEDED.
Ventilation:USE MECHANICAL (GENERAL) VENTILATION IS SUFFICIENT DURING
NORMAL USE & HANDLING. 2-3 ROOM CHANGES/HOUR ARE RECOMMENDED.
Protective Gloves:RUBBER OR NEOPRENE GLOVES.
Eye Protection:GOGGLES OR SAFETY GLASSES + FACE SHIELD
Other Protective Equipment:ACID RESISTANT APRON OR CLOTHING.
Work Hygienic Practices:MAINTAIN EYEWASH & DRENCH SHOWER IN AREA.
Supplemental Safety and Health
CONTACT C & D SALES REPRESENTATIVE FOR INFORMATION ON BATTERY (LEAD &
ACID) RECYCLING.
Chemical Properties
HCC:C1
NRC/State Lic Num:NONE
Boiling Pt:B.P. Text:235F,113C
Melt/Freeze Pt:M.P/F.P Text:N/A.
Vapor Pres:145.8 MM
Vapor Density:<1
Spec Gravity:1.215-1.290
Evaporation Rate & Reference:<1 , WATER=1
Solubility in Water:100%
Appearance and Odor:CLEAR COLORLESS LIQUID, ACRID SMELL.
Corrosion Rate:UNKNOWNN
Stability
Stability Indicator/Materials to Avoid:YES
METALS, COMBUSTIBLES.
Stability Condition to Avoid:THIS IS A STABLE MATERIAL.
Hazardous Decomposition Products:HYDROGEN GAS, SULFUR TRIOXIDE MAY BE
GENERATED DURING BATTERY OVERCHARGE & AT HIGH TEMPERATURES.
Conditions to Avoid Polymerization:WILL NOT OCCUR.
Disposal
Waste Disposal Methods:BATTERY ACID IS A CORROSIVE HAZARDOUS WASTE.
WHEN NEURTALIZED TO PH 6-8 IT IS NO LONGER HAZARDOUS. FOLLOW PROPER
DISPOSAL METHODS AS ALLOWED BY LOCAL ORDINANCES & SITE PERMITS.
ACID IN SCRAP BATTERIES WILL BE RECYCLED BY THE LEAD
RECYCLINGPROCESS.
Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.